How can we help you today?

My Smart UPS Modular Ultra shows "Battery not compatible"

Issue:

My Smart UPS Modular Ultra shows "Battery not compatible"


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

There are three options for clearing this alarm:

  1. Upgrade the UPS to at least FW 17.0 for a permanent fix (Recommended)
  2. Wait four hours for the next compatibility check - the error usually clears the next time the system checks for compatibility
  3. Power cycle the battery using the thumbscrew on the front of the battery module - this will clear the error and restart communications

If the issue still persists, the battery will need to be replaced.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings