Question: How can I get a list of points linked to a particular email action within my Geo SCADA Database?

You can retrieve this information using a SQL query. Here's how:

The Query:

SELECT

O.ID,

O.FULLNAME,

R.ACTION1ID->FULLNAME

FROM

CALARMREDIRECTIONLIST AS R

JOIN

CDBOBJECT AS O ON R.ID = O.ID

WHERE

R.ACTION1ID = 5347 -- Replace 5347 with the actual Email Action ID

ORDER BY

"FullName" ASC

Note: As per the highlighted section above, replace the number 5347 with the object ID number of the email action object.