What value is expected when measuring capacitance of individual capacitors in a Powerlogic PFC capacitor bank?
Issue:
It may not be clear what value is to be expected when measuring capacitance for capacitors in a Powerlogic PFC capacitor bank.
Product Line:
Powerlogic PFC capacitors
Resolution
There will be a uF rating on the label of the capacitor. The L-L measurement taken should be 1.5X the value printed on the capacitor label. The photo below shows a typical label and where this value can be found.
Example: BLRCH292A350B57, the capacitance per phase for this capacitor is 93.8uF. 93.8 X 1.5 =140.7uF
You would need to measure line to line (A to B, B to C, and C to A) on the capacitor and the values should be around 140uF -/+5% for each measurement.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.