Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Explanation of the 'context' described for the power supply in the M580 User manual.

https://download.schneider-electric.com/files?p_Doc_Ref=EIO0000001578&p_enDocType=User+guide
werthj

The context corresponds to the last state of the customer application, for example if the CPU was sending a communication to a device during the power outrage, it will save the state and allow the warm start. It will restart from the beginning of the communication to continue the application process where it has stopped before the outrage. The context is supposed to be saved without being lost, the only way to change the context is to power down the system. This will also depend on the health of the memory.

If the context is valid this will allow the CPU warm start.  Otherwise, this will result in a cold start from which the CPU is completely restarts the application from the beginning.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings