Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to view the real time logic address of Altivar Drives?

Issue:

How to view the real time register or bits within these Input and Output Scanner Modbus Registers?

Product Line:

ATV630, ATV930, ATV340

Environment:

All serial numbers

Cause:

This has to do with troubleshooting capabilities.

Resolution:

In SoMove, there are three options to see the values of registers.

1) Under Display -> Communication Mappings

SoMove_1

2) The second option is to create your own display by clicking on "Motor" and "Drive" then highlight and pull the registers to the empty space to create your own display.

SoMove_2

The third option is to add the parameter for visualization on Dashboard/Display section, by its Logical Address - example is LFRD:

SoMove_3

For legacy drives like ATV61/71/320 - the feature in SoMove is not available.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings