Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
M580 Hot Standby Device DDT type : T_M_ECPU_HSBY vs T_M_ECPU_HSBY_EXT

Issue :

When working with M580 Hot Standby application, why do I sometimes see the Device DDT type T_M_ECPU_HSBY and other times T_M_ECPU_HSBY_EXT

Products :

Control Expert (Unity Pro)

M580 Hot Standby

Answer :

This is based on the application level of your application.

If you have an application defined with an M580 of 2.70 and lower, you will see the T_M_ECPU_HSBY.

M580 2.70

If you have an application defined with an M580 of 2.80 and higher, you will see the T_M_ECPU_HSBY_EXT.

M580 2.80

In the PDF attached the differences between the 2 types have been identified.

Schneider Electric USA

Attachment(s)
M580 Hot Standby Device DDT differences.pdf [182.82 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings