Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Smart UPS Modular Ultra Reports Inaccurate Low Runtime

Issue:

My Smart UPS Modular Ultra has reports an inaccurate low runtime on the display/NMC.


Product Line:

Smart UPS Modular Ultra


Resolution:

On UPS Firmware 13.3 or earlier, the runtime may be linked to the battery with the lowest capacity only.  In UPS Firmware 15.0 and later, there is an improvement to the runtime accuracy when a low capacity battery module is installed.

Please install UPS Firmware 15.0 or later.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings