Released for: Schneider Electric USA | Published on: 06/22/2026 | Last modified on: 08/03/2026 | Author: Customer support team

On this page
Selecting products and product info

The installer password can be changed. However the module must be in the standard mode by setting the rotary switch located at the back of the module.  Once in standard mode, log into the module via your browser using the default user name and password. once connected, you will see "Installer" in green in the top right corner of the browser. click on it, and you will see the option to change password.

The HTTPS service of the BMENUA0100 OPC UA module can be disabled. The module must be in secure mode to disable the service. Once you are logged in, go to the "cyber security setup" tab then select "settings" then select "network services"

Below are the steps to Configure the cybersecurity settings of the OPC UA server module:

1. With the module detached from the rack, use the plastic screwdriver that ships with the module to set the rotary switch to the [Secured] position.
2. Install the module into an Ethernet slot on the local, main Ethernet rack and cycle power.
3. Use your Internet browser to connect your configuration PC to the module, using either the control port or the backplane port, and navigate to the module web pages at the configured IP address.
4. If your Internet browser displays a message indicating a potential security risk, proceed to make the connection by clicking Accept the Risk and Continue (or similar, browser-specific language).
5. In the user login page, enter the default username / password combination.
6. Change and confirm the password. Refer to the User Management topic for password requirements. The module Home page is displayed.
7. Starting from the Home page, navigate to the module web pages and configure its cybersecurity settings.

The default number of times a user may attempt, and fail, to login is five(5). When the configured maximum is reached, the user account is locked. A locked user account is automatically unlocked after 4 minutes(default value).

The BMENUA0100 module support only NTP V4. It is not backwards compatible with NTP V3.
Installing, operating and maintenance

Current consumption of BMXP342020 is 95 mA 24 V DC.

Yes, you can. To accomplish this, follow the steps below:
NOTE: In order for changes to be made from one protocol to another, the processor serial port must be configured for Modbus Slave mode.

1.First create an IODDT variable linked to the processor’s serial channel, then set the bit that corresponds to the protocol desired:

  • TO_MODBUS_MASTER(%MWr.m.c.24.12) (Bit 12): Current protocol is changed to Modbus Master.
  • TO_MODBUS_SLAVE(%MWr.m.c.24.13) (Bit 13): Current protocol is changed to Modbus Slave.
  • TO_CHAR_MODE(%MWr.m.c.24.14) (Bit 14): Current protocol is changed to Character Mode.
2.Then initiate the WRITE_CMD for the channel. Whenever the mode(Master to Slave or Slave to Master) is changed, a WRITE_CMD must be executed. The WRITE_CMD can be triggered on a rising edge. No need to write every scan. See the sample code below.

3.You can now read/write the data to the remote device using explicit exchange messaging such as the READ_VAR, WRITE_VAR or DATA_EXCH function blocks.

The I/O scanner for the M340 NOE modules supports Function Codes 3,16 and 23.

The NUA module does not have a buffer to hold events. If comms go down then the events will be lost. Buffering or holding events is not in the OPC UA spec.

For RS232 communication between the Magelis XBTF and M340 PLC, the cable pinout should be as follow:

The M340 serial port must be configured for RS232 as shown below

The XBTF configuration should match the serial port setup of the M340.

Below is a sample code on how to configured the READ_DDT function block


Below is a sample code using the READ_DDT function block to read messages from the BMENUA0100 communication module.
Note: Ensure that the RECP_DDT variable has the data type "T_BMENUA0100" DDT

The cable pinout between the M340 PLC embedded serial port configured for RS232 and the HMIGTO Com 1 is shown below

image

The number of connections the BMENUA0100 module can open to the M580 CPU depends on the capacity of the CPU. Thus, performance of the BMENUA0100 module will depend on the time required to perform the MAST task and the selected CPU. The maximum number of connections opened by each BMENUA0100 module to the M580 CPU are as follows:

This table below lists all possible connection types between the HMIST6/HMISTM6 models and the M340 PLC with the associated required Serial Cable:

HMI Part NumberHMI Serial PortSerial Communication StandardCable Part Number
HMIST6200COM1 (RJ45)RS-485XBTZ9980
HMIST6400COM1 (Dsub9)RS-232TCSMCN3M4F3C2
HMIST6400COM2 (RJ45)RS-485XBTZ9980
HMIST6500COM1 (Dsub9)RS-232TCSMCN3M4F3C2
HMIST6500COM2 (RJ45)RS-485XBTZ9980
HMIST6600COM1 (Dsub9)RS-232TCSMCN3M4F3C2
HMIST6600COM2 (RJ45)RS-485XBTZ9980
HMIST6700COM1 (Dsub9)RS-232TCSMCN3M4F3C2
HMIST6700COM2 (RJ45)RS-485XBTZ9980
HMISTM6200COM1 (RJ45)RS-485XBTZ9980
HMISTM6400COM1 (RJ45)RS-485XBTZ9980

No, The Unity Loader cannot be used for upgrading the firmware of the OPC UA module. You must use the EcoStruxure Automation Device Maintenance utility. You can download the utility and firmware file from the Schneider Electric public site at EcoStruxure Automation Device Maintenance V3.4.120 :https://www.se.com/us/en/download/document/EADM/

BMENUA0100 OPC UA module firmware: https://www.se.com/us/en/download/document/BMENUA0100_FIRMW_SV_02_04_02/

This article is valid for the X80 modules offer, M580 communication modules , M580 Safety Processor and the Control Expert L or XL with M580 Safety Add On software

TÜV certified Control Expert versions and hot fixes:

With certificate 01/205/5610.02/22 and the latest revision version 5.0 .

For safety PLC programming the approved TÜV versions of Control Expert and released hot fixes (HF) are the following:

Control Expert L or XL with M580 Safety Add On list Part 1
Control Expert L or XL with M580 Safety Add On list Part 2

TÜV certified M580 Safety Processors, M580 communication modules and X80 modules:

In the revision list, you can also find the status of the different X80 modules, communication modules and M580 Safety Processors.

X80 modules
Part of the X80 modules list
Note: The above image is only one part of the list of X80 modules.

M580 communication modules
M580 communication modules
Note: The above image is only one part of the list of M580 communications modules.

M580 Safety Processors
M580 Safety Processors

Check the TÜV certification status:

To check if a software version of Control Expert or Hot fix is TÜV certified or if it is certified to date, we must do the following:

  • Go to: https://www.certipedia.com/
  • In Search tool prompt “M580”, then select the newest certificate from the SCHNEIDER ELECTRIC certificate holder.
Select latest M580 certificate
  • Then click on the list located in Appendixes.
From the Certificate select Appendixes
  • And then search for the hardware part, software version or hot fix you need.

If the hardware, software version or hot fix is not in the list, it means it is not TÜV certified.

This is not a 'safety module' but rather a 'non-interfering' one. It will not have direct access to anything related to the safety side, only the process side.

Videos
How do I upgrade the firmware of the BMENUA0100 OPCUA server module?
Product services, support, and warranty

The color code for the BMXFCW301S & BMXFCW501S is shown below.

Wire Color Code and Reference
How to Videos
How do I upgrade the firmware of the BMENUA0100 OPCUA server module?
Explore More
Range:Products:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings