Is there an EIFE module available for fixed-type version of MTZ breakers?

Article available in these languages: Spanish

Issue:

Installing the EIFE on fixed MTZ breaker version

Product Line:

Masterpact MTZ1, MTZ2, MTZ3

Resolution:

No, the EIFE (Embedded Ethernet Interface) module is not available for fixed-type Masterpact MTZ breakers. It is designed exclusively for drawout-type MTZ1, MTZ2, and MTZ3 breakers.

The EIFE module requires the ULP port for drawout breakers that goes mounted on the cradle. Therefore, it cannot be mounted or connected to fixed-type breakers. If you're working with fixed MTZ breakers and need Ethernet connectivity or remote monitoring, you can use an IFE module.

Related Part Numbers:

LV851200SP – Replacement EIFE kit for drawout-type breakers

LV851001SP – Standalone EIFE module replacement for drawout breakers

LV434001 - IFE Ethernet interface for one breaker

LV434002 - IFE Ethernet interface gateway

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings