EM3570 Series Diagnostic Error Codes

Issue

I have an error code on my EM3570 series meter.

Product Line

EM3570, EM3570A, EM3570X, EM3570AX

Environment

Energy Meter Diagnostic

Cause
EM3570 Series meter has a diagnostic error code

Resolution
Please see below for the EM3570 Series Diagnostic Error code, Description, and possible solution.

Diagnostic Code Description possible solution
(no code)LCD display not visibleCheck and adjust LCD contrast / backlight setting.
(no code)Push buttons do not functionRestart the meter by powering off and powering on again.
101,102Metering stops due to internal error, Total energy consumption is displayed.Enter the configuration mode and implement Reset Config.
201Metering continues. Mismatch between frequency settings and frequency measurements. Correct frequency settings according to the nominal frequency of the power system.
202Metering continues. Mismatch between wiring settings and Wiring inputs. Correct wiring settings according to wiring inputs
203Metering continues. Phase sequence reversed. Check wire connections and correct wiring settings, if needed
205Metering continues. Date and time have been reset due to loss of power. Set date and time.
206Metering continues. Pulse is missing due to overload on energy pulse output. Check the energy pulse output settings
207Metering continues. Abnormal internal clock functionRestart the meter by powering off and powering on again then reset the date and time.
301Internal communication ErrorCheck for proper Ethernet cable connection. If the diagnostic code persists for more than 2 minutes, contact technical support.
303IP conflict Check the duplicate IP in the network and assign unique IP for each meter.
304IP not set (default IP) Assign the meter with unique IP
(no code) Unavailability of webpages due to multiple user account loginsWait for 10 s to re-login.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings