PowerChute Network Shutdown does not stop Nutanix cluster.

Issue:

When PowerChute Network Shutdown commands a Nutanix cluster to shut down, the cluster does not shut down as expected.

Product:

PowerChute Network Shutdown 5.x

Environment:

Nutanix AOS 7.3 and above with AHV and ESXi

Cause:

Starting with AOS 7.3, the terminal multiplexer (TMUX) is enabled by default when an SSH session is initiated. This prevents PowerChute from successfully sending the cluster stop command.

Solution:

Disable TMUX. Refer to the Nutanix Knowledge Base article for instructions on disabling TMUX.

https://portal.nutanix.com/page/documents/kbs/details?targetId=kA0VO0000007KGX0A2

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings