What subfeed options are available in SB324QR?

Issue:
Subfeed circuit breaker compatibility and wire size requirements for SB324QR Speed D Switchboard

Product Line:
Schneider Electric Speed D Switchboard – SB324QR

Resolution:
The SB324QR Speed D Switchboard includes provisions for installing two HLP or JLP subfeed circuit breakers. The loadside lug capabilities vary depending on the frame and ampacity of the breaker selected:

  • H Frame (100–150A): Accepts wire sizes from #14 to 3/0 AWG
  • J Frame (175A): Accepts wire sizes from #4 to 4/0 AWG
  • J Frame (200–225A): Accepts wire sizes from 3/0 to 350 kcmil

These provisions allow for flexible subfeed configurations based on your specific load requirements and the selected breaker type.

For additional technical documentation, including dimensions and drawings, refer to the online Digest or Schneider Electric’s product selector tools.

Schneider Electric USA

Attachment(s)
SB324QR.png [16.29 KB]
SB324QR (2).pdf [76.95 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings