What is the switching life and mechanical life of a vacuum contactor?

Article available in these languages: Spanish

Issue:
What is the switching life and mechanical life of a vacuum contactor?

Product Line:
Motorpact™ 200/400/450 A Vacuum Contactors

Environment:
Replacement and maintenance planning

Cause:
Determining when it is necessary to replace the vacuum interrupter based on operational limits.

Resolution:

  • Switching Life: The vacuum interrupter should be replaced after reaching its switching life of 250,000 operations.
  • Mechanical Life: The overall mechanical life of the contactor is rated at 2,500,000 operations.

Source:
Motorpact™ 200/400/450 A Vacuum Contactors – Instruction Bulletin 46032-700-02D (03/2011)