Correct Wiring for External CT with LTMR Devices

Title:

Correct Wiring for External CT with LTMR Devices

Issue:

How should the external current transformer (CT) be wired to the LTMR device?

Product Line:

LTMR (Motor Protection and Control Devices)

Environment:

LTMR device with external CT connection (CT terminals labeled S1/S2)

Resolution:

Your CT must have two terminals (S1 and S2). The wiring should be as follows:

  • The wire must leave S1, pass through the internal CT of the LTMR, and then land on the second terminal S2.
    This ensures proper current measurement and device functionality.

Schneider Electric USA

Attachment(s)
CTs for Tesys T.png [52.45 KB]