Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Nutanix Files Start fails if sufficient time is not allowed after cluster is started.

Issue:

Nutanix Files Start command fails when issued shortly after cluster startup completes.

The following message appears in the error.log file -

2025-12-10T01:07:15,435 ERROR Thread-32 com.apcc.pcns.nutanixservice.NutanixSshConnection - startAfs() - AFS start command failed with result ERROR: Unable to power on vms for fileserver

2025-12-10T01:07:15,435 ERROR pool-9-thread-1 com.apcc.m11.components.shutdowner.NutanixClusterOps java.util.concurrent.ExecutionException: java.rmi.RemoteException: Failed to start AFS
at java.base/java.util.concurrent.CompletableFuture.reportGet(CompletableFuture.java:396) - startAFS() - failed to start AFS: {}

Product:

PowerChute Network Shutdown version 5.2

Environment:

Nutanix AHV 10.3, AOS 7.3

Cause:

The Files Start command fails when issued shortly after the cluster startup completes.

Solution:

Increase Cluster Start duration to allow enough time between cluster start and attempt to re-start Nutanix Files. This may need to be set between 10 and 15 minutes.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings