How can we help you today?
IRIG‑B Interface Options for P7 Relay Using BNC Connection
Issue
Can the IRIG‑B port on a P7 relay interface using a BNC cable, and is any adapter or converter required?
Product
Powerlogic P7 Protection Relay
Environment
Systems using IRIG‑B time synchronization distributed via BNC‑terminated cabling.
Cause
The P7 relay does not have a native BNC IRIG‑B input, leading to the need for an appropriate interface option.
Resolution
Yes, the P7 relay can receive an IRIG‑B signal through a BNC cable by using the IRIG-B time synchronization module, part number REL51045 module, which connects to the P7 relay’s EXT IN port and enables proper IRIG‑B input.
The characteristics of the IRIG-B module are:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.