Resolving System Information Code 3154 During Edge Certificate Installation
Overview
This article provides guidance for troubleshooting System Information Code 3154 (Metadata 31) encountered when loading an Edge application certificate using Remote Connect on a SCADAPack device.
Issue Description
After loading the Edge application certificate through Remote Connect:
- The system displays Code 3154
- Metadata value: 31
Possible Causes
- Operator Selector Mode not set correctly
- Invalid or corrupted certificate
Certificate not properly applied to the system
Resolution Steps
Step 1: Verify Device Configuration
Ensure the following before proceeding:
- The Operator Selector Mode is set to F mode
- The certificate being used is valid
If there is any uncertainty about the certificate, regenerate and use a fresh copy.
Step 2: Reset Diagnostics
Click on Reset Diagnostics in Remote Connect.
Recheck the System Information Code.
Expected Result
- The code should reset to 0
Step 3: Evaluate the Result
Case 1: Code is NOT 0
- Attempt to reload the certificate manually
Case 2: Code is 0
- Proceed to validate the certificate manually using SSH
Step 4: Validate Certificate via SSH
Connect to the Device
- Open PuTTY (or any SSH client).
- Connect via USB using the following IP: 10.2.3.4
- Log in with:
- Username: root
- Password: (configured password)
Verify Certificate Installation
Run the following command:
ls -la /mnt/sec_data/rauc/certs; cat /mnt/sec_data/rauc/certs/integrator.crt