How can we help you today?

How to Identify the Correct Device Type for Micrologic Trip Unit

Issue:

Sometimes when connecting a Micrologic Trip Unit to a system such as, Power Monitoring Expert (PME), it can present an error message "Translator Failure" or not show the proper values. This may be an indication that the incorrect device type is being used for this device in the program. To verify if this is the case, the device type for the unit can be identified by reading a specific Modbus register.


Product Line:
Micrologic A

Micrologic E

Micrologic P

Micrologic H

Environment:
Modbus Reading Program

Resolution:

To do this process, you will need a tool that can read Modbus registers. If you do not have a preferred program for this action, you can download the attached Modbus Tester program from this article Video: What is Modbus Tester and how do I use it? | Schneider Electric USA.

In order to figure out which trip unit product is being used, we will need to identify which Modbus register will return the proper code. On pg. 136 of the user guide found in the link and attached to the article, What are the Modbus registers for Micrologic A, P, and H trip units used in Powerpact P, R, and Masterpact NW/NT breakers? | Schneider Electric USA, under the "Product Identification" section it shows the register to read to get the device type returned to you for identification.

In the screenshot below, when you read Holding Register (R03 / W16): 8716 (full register value being 408716) it will return the type of the trip unit. Based on the number returned you will be able to identify if it is one of the trip unit types below Micrologic A, Micrologic E, Micrologic P, or Micrologic H.

product identification

Schneider Electric USA

Attachment(s)
All A, P, H Registers (1).pdf [9.51 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings