How can we help you today?

Why does the BMENOP0300 not retrieve archived BRCB reports from an IED?

The Modicon BMENOP0300 is configured as an IEC 61850 client and connected to an external IED server.

After a communication interruption, the IED stores buffered reports in its BRCB buffer.

This FAQ will clarify why once communication is restored, the BMENOP0300 does not retrieve the reports generated during the disconnection period through its report history function.

This FAQ is valid in an environment with:

  • EcoStruxure Control Expert V16 & later
  • BMENOP0300 FW V 2.71 IR5 & later
  • Modicon IEC 61850 Configuration Tool V 3.41 IR07 & later
  • BMENOP0300 configured as an IEC 61850 client
  • External IEC 61850 IED server
  • Buffered Report Control Blocks (BRCB) configured on the IED server

For the BMENOP0300 history function to manage reports previously stored in the IED server BRCB buffer, the following optional fields must be included in the reports generated by the IED:

  • EntryID
  • TimeOfEntry, represented by the Timestamp option

EntryID identifies the buffered report, while TimeOfEntry provides the time associated with its entry into the IED buffer. Without these fields, the BMENOP0300 cannot apply the expected chronological history-management mechanism.

The module documentation also requires NTP time synchronization between the BMENOP0300 and the external IED servers.

In order to fix this issue,  please follow the recommendations below:

1. Verify the BRCB configuration in the IED:

When possible, configure the IED server device directly so that its BRCB OptFlds attribute includes:

  • EntryID
  • TimeOfEntry

The OptFlds value determines which optional fields the IED includes in each generated report.

2. Modify OptFlds from the BMENOP0300:

If the IED allows the BMENOP0300 client to write the BRCB configuration (OptFlds), the options can be modified through the BRCB control structure in the Device DDT:

  • Option = 106: Read the current OptFlds value
  • Option = 6: Write a new OptFlds value
  • Attribute: Contains the value read from or written to OptFlds

NOP DDT 1

Recommended read-modify-write procedure

  • Use mask for enabling both EntryID and TimeOfEntry, and keeping the other Optflds fields already configured on the IED, such as sequence number, reason for inclusion, data set name, data reference or configuration revision.

The mask value is 8448 in decimal, or 0010 0001 0000 0000 in binary.

  • Use a read-modify-write sequence :
  1. Disable the BRCB report
  2. Read OptFlds using Option = 106
  3. Retrieve the current value from Attribute
  4. Apply the required bit mask
  5. Write the calculated value to Attribute
  6. Execute the write using Option = 6
  7. Read OptFlds again using Option = 106
  8. Confirm that only the intended bits changed
  9. Re-enable the BRCB report

This procedure preserves the other optional fields already configured in the IED.

Enabling EntryID and TimeOfEntry

Apply a bitwise OR operation:   (New OptFlds value) = (Current OptFlds value) OR (8448)

Example:

Current value : 22016
Mask:             : 8448

Therefore: 22016 OR 8448 = 30464  => Write 30464 into Attribute with Option = 6.

Disabling EntryID and TimeOfEntry

Apply a bitwise AND NOT operation:  (New OptFlds value) = (Current OptFlds value) AND NOT (8448)

Example:

Current value : 32640
Mask              : 8448

Therefore: 32640 AND NOT 8448 = 24192  => Write 24192 into Attribute with Option = 6.

Additional checks

Report selection

In the Modicon IEC 61850 Configuration Tool (IEDCT), confirm that the required BRCB is selected for report backfill. Selecting the report creates the corresponding variables in the CLIENT_HISTORY_<module name> Device DDT.

History mode

Confirm that one of the following modes is selected:

  • History-Cyclic: The BMENOP0300 exposes archived reports periodically according to BACKFILL_REFRESH_RATE variable in its Device DDT.
  • History-OnDemand: The application retrieves archived reports individually through ONDEMAND_FLAG variable in its Device DDT.

IEDCT1

NTP synchronization

Configure the BMENOP0300 and the IED servers to use synchronized NTP time sources. Unsynchronized clocks can prevent consistent chronological processing of archived BRCB reports.

Best Regards.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings