Schneider Electric USA Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
View all   Zelio Control
Schneider Eletric RM35TM250MW Picture

RM35TM250MW

Green premium brand logo
Schneider Eletric RM35TM250MW Picture
RM35TM250MW
Green premium brand logo

motor voltage and temperature control relay - RM35-T - 24..240 V AC/DC - 2 NO

Show more characteristics
  • Product availability
    Non-Stock - Not normally stocked in distribution facility
  • 231.00 USD
    Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range of product
    Zelio Control
    product or component type
    Modular measurement and control relays
    relay type
    Motor temperature control relay
    product specific application
    For 3-phase supply
    relay name
    RM35TM
    relay monitored parameters
    Phase failure detection
    Phase sequence
    Test/reset button
    Motor temperature via PTC probe
    Selection (with or without memory)
    time delay
    Fixed 0.3 s
    switching capacity in VA
    1250 VA
    measurement range
    208...480 V voltage AC
    0...20 Ohm short-circuit detection
    Complementary
    reset time
    10000 ms output
    maximum switching voltage
    250 V AC
    250 V DC
    minimum switching current
    10 mA 5 V DC
    maximum switching current
    5 A AC
    5 A DC
    supply voltage limits
    20.4…264 V AC
    20.4…264 V DC
    power consumption in VA
    0…4 VA 24...240 V AC
    power consumption
    0.5 W DC
    control circuit frequency
    50...60 Hz +/- 10 %
    resistance across terminals
    602 mOhm
    output contacts
    2 NO
    nominal output current
    5 A
    measurement voltage limits
    176…528 V AC
    delay at power up
    500 ms
    voltage range
    176...528 V
    response time
    > 50 ms input Y1 (contact Y1-T1) and push-button)
    [Uc] control circuit voltage
    <= 3.6 V temperature control circuit T1-T2 terminals open)
    short-circuit current
    0.007 A temperature sensing circuit T1-T2 terminals short circuited)
    maximum resistance
    1500 Ohm temperature sensor 68 °F (20 °C)
    tripping threshold
    3100 Ohm +/- 10 % temperature control circuit
    reset threshold
    1650 Ohm +/- 10 % temperature control circuit
    marking
    CE
    overvoltage category
    III IEC 60664-1
    insulation resistance
    > 500 MOhm 500 V DC between supply and relay output IEC 60255-5
    > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1
    > 1 MOhm 500 V DC between supply and measurement IEC 60255-5
    > 500 MOhm 500 V DC between supply and relay output IEC 60664-1
    > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5
    > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
    [Ui] rated insulation voltage
    400 V IEC 60664-1
    supply frequency
    50/60 Hz +/- 10 %
    operating position
    Any position without derating
    connections - terminals
    Screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
    tightening torque
    5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
    housing material
    Self-extinguishing plastic
    local signalling
    Power ON LED green)
    Phase of relay (R2) LED yellow)
    Temperature of relay (R1) LED yellow)
    mounting support
    35 mm symmetrical DIN rail EN/IEC 60715
    electrical durability
    10000 cycles
    mechanical durability
    30000000 cycles
    operating rate
    <= 360 operations/hour full load
    utilisation category
    AC-12 IEC 60947-5-1
    AC-13 IEC 60947-5-1
    AC-14 IEC 60947-5-1
    AC-15 IEC 60947-5-1
    DC-12 IEC 60947-5-1
    DC-13 IEC 60947-5-1
    Maximum Width
    1.38 in (35 mm)
    Net Weight
    0.29 lb(US) (0.13 kg)
    Environment
    immunity to microbreaks
    20 ms 20.4 V
    electromagnetic compatibility
    Emission standard for industrial environments EN/IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3
    Immunity for industrial environments EN/IEC 61000-6-2
    standards
    EN/IEC 60255-6
    IEC 60034-11-2
    product certifications
    CSA
    C-tick
    GOST
    UL
    GL
    directives
    73/23/EEC - low voltage directive
    89/336/EEC - electromagnetic compatibility
    ambient air temperature for storage
    -40…158 °F (-40…70 °C)
    ambient air temperature for operation
    -4…122 °F (-20…50 °C)
    relative humidity
    95 % 131 °F (55 °C) IEC 60068-2-30
    vibration resistance
    0.35 mm 5…57.6 Hz)IEC 60068-2-6
    1 gn 57.6…150 Hz)IEC 60255-21-1
    shock resistance
    15 gn 11 ms IEC 60255-21-1
    IP degree of protection
    IP20 IEC 60529 terminals)
    IP30 IEC 60529 casing)
    pollution degree
    3 IEC 60664-1
    dielectric test voltage
    2 kV AC 50 Hz, 1 min
    non-dissipating shock wave
    4 kV
    Ordering and shipping details
    Category
    22380 - RELAYS-MEASUREMENT (RM17-RM35)
    Discount Schedule
    CP2
    GTIN
    00785901869498
    Nbr. of units in pkg.
    1
    Package weight(Lbs)
    0.29 lb(US) (0.13 kg)
    Returnability
    No
    Country of origin
    ID
    Packing Units
    Package 1 Height
    0.780 dm
    Package 1 width
    0.450 dm
    Package 1 Length
    0.970 dm
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    California proposition 65
    WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    Contractual warranty
    Warranty
    18 months
  • View more View less

    Documents

    Language
    • All Languages19
    • English18
    • French5
    • German4
    • Italian4
    • Spanish4
    Catalog
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 8.1 MB
    Date 6/24/19
    prp.document.label.format pdf
    Size 6 MB
    Date 5/12/19
    prp.document.label.format pdf
    Size 7.1 MB
    Date 6/24/19
    Certificate
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 3 MB
    Date 5/23/19
    UL Listed RM17, RM22, RM35, RM8487 (Version 1.0)
    Files in document
    pdf
    475.7 KB
    pdf
    473.4 KB
    prp.document.label.format zip
    Size 949 KB
    Date 5/19/15
    Files in document
    pdf
    475.7 KB
    pdf
    473.4 KB
    prp.document.label.format htm
    Size 213 B
    Date 5/18/15
    Instruction Sheet
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 418.1 KB
    Date 6/1/20
    prp.document.label.format pdf
    Size 332.8 KB
    Date 1/1/08
    China RoHS declaration
    Format
    Size
    Date
    Add to My Documents
    RM35TM250MW : RM35TM250MW_ROHS_CHINA_DECLARATION
    Description
    RM35TM250MW_ROHS_CHINA_DECLARATION
    prp.document.label.format pdf
    Size 195.3 KB
    Date 7/6/20
    Description
    RM35TM250MW_ROHS_CHINA_DECLARATION
    End of Life Information
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 5.4 MB
    Date 5/1/19
    prp.document.label.format pdf
    Size 89.6 KB
    Date 2/1/16
    prp.document.label.format pdf
    Size 582.8 KB
    Date 11/1/11
    EU RoHS Declaration
    Format
    Size
    Date
    Add to My Documents
    RM35TM250MW : RM35TM250MW_ROHS_DECLARATION
    Description
    RM35TM250MW_ROHS_DECLARATION
    prp.document.label.format pdf
    Size 195.3 KB
    Date 7/6/20
    Description
    RM35TM250MW_ROHS_DECLARATION
    Product Environmental Profile
    Format
    Size
    Date
    Add to My Documents
    prp.document.label.format pdf
    Size 5.4 MB
    Date 5/1/19
    prp.document.label.format pdf
    Size 3.3 MB
    Date 1/1/16
    prp.document.label.format pdf
    Size 2.2 MB
    Date 11/1/11
    REACh Declaration
    Format
    Size
    Date
    Add to My Documents
    RM35TM250MW : RM35TM250MW_REACH_DECLARATION
    Description
    RM35TM250MW_REACH_DECLARATION
    prp.document.label.format pdf
    Size 195.3 KB
    Date 7/6/20
    Description
    RM35TM250MW_REACH_DECLARATION
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    3-Phase Supply and Motor Temperature Control Relays
    Dimensions and Mounting



  • Connections and Schema

    3-Phase Supply and Motor Temperature Control Relays
    Wiring Diagram



  • Technical Description

    Function Diagrams
    Phase Sequence Control and Phase Failure Detection (U measured < 0.7 x nominal supply voltage)


    Motor Temperature Control via PTC Probe


    Legend

    Un Nominal 3-phase supply voltage

    R T1-T2 Resistance between terminals T1 and T2

    11-14 R1 output relay connections

    Relay status: black color = energized.

    NOTE: The temperature control relay can take up to 6 PTC (positive temperature coefficient) probes wired in series between terminals T1 and T2.


    Function Diagrams
    Motor Temperature Control via PTC Probe

    As soon as the temperature returns to the correct value, the relay can be unlocked (reset), either by pressing the “Test/Reset” button (for at least 200 ms), or by closing a volt-free contact (for at least 200 ms) between terminal Y1 and T1 (without a parallel load). When a fault is detected, the “temperature” output relay locks in the open position, even if the “Test/Reset” button is pressed.

    With memory ("Memory" mode)


    Use of the “Test/Reset” Button

    When the temperature is normal, pressing the “Test/Reset” button simulates overheating, the “temperature” output relay contact is open.

    Without memory ("No Memory" mode).


    With memory ("Memory" mode)


    Legend

    Un Nominal 3-phase supply voltage

    R T1-T2 Resistance between terminals T1 and T2

    11-14 R1 output relay connections

    Relay status: black color = energized.

    In "Memory" mode, “fault” indication is locked and the button must be released then pressed again to reset the function. When a fault has been detected and the temperature has returned to normal, the “temperature” control relay can be unlocked (reset) by pressing the “Test/Reset” button.