{}

Nhãn hiệu của chúng tôi

Impact-Company-Logo-English Black-01-177x54

Chào mừng bạn đến với Trang web của Schneider Electric

Chào mừng đến với trang web của chúng tôi.
Tìm các câu hỏi thường gặp
Are drive thermal output ratings available in BTU?
Issue:
Are drive thermal output ratings available in BTU?

Product Line:
All Altivar Drives, Machine, Process, Buildings

Resolution:
Heat dissipation is listed in Watts only in the Installation Manuals for the individual product.

See the drive catalog or installation manual for specific details on the heat dissipation per the exact part number.
1 watt is approximately 3.41 BTU/h
1000 BTU/h is approximately 293 W

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)



Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Bài viết có thể hữu ích
Tìm hiểu thêm
Phạm vi: