Issue:
External 24vdc digital output from PLC wiring to the input of the ATV21/212 drives?
Product Line:
Altivar ATV21 or ATV212
Environment:
All
Cause:
Needs to wire in an external 24vdc digital output from a PLC into the drive.
Resolution:
Make sure the Source, CLP, Sink dip switch is set to CLP.
Example of PLC with a sourcing output.
ON the ATV21 or ATV212 drive jumper PLC and CC together. Then wire the PLC and CC to 0V on the external PLC or Power supply.
Next run your external 24vdc digital output from your PLC controller to the F, R or RES inputs of the drive.
Example of PLC with a sinking output.
On the ATV21 or ATV212 drive jumper CC to 0V and jumper the ATVs PLC connection to external +24vdc supply.
The PLC controllers output will wire to F, R, RES inputs of the drive.
See attachment for example
External 24vdc digital output from PLC wiring to the input of the ATV21/212 drives?
Product Line:
Altivar ATV21 or ATV212
Environment:
All
Cause:
Needs to wire in an external 24vdc digital output from a PLC into the drive.
Resolution:
Make sure the Source, CLP, Sink dip switch is set to CLP.
Example of PLC with a sourcing output.
ON the ATV21 or ATV212 drive jumper PLC and CC together. Then wire the PLC and CC to 0V on the external PLC or Power supply.
Next run your external 24vdc digital output from your PLC controller to the F, R or RES inputs of the drive.
Example of PLC with a sinking output.
On the ATV21 or ATV212 drive jumper CC to 0V and jumper the ATVs PLC connection to external +24vdc supply.
The PLC controllers output will wire to F, R, RES inputs of the drive.
See attachment for example
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.