CANOPEN run light never stops blinking when the address is correctly assigned to the NCO2212
Issue
CANOPEN run light never stops blinking when the address is correctly assigned to the NCO2212
Product Line
NCO2212
Environment
Windows 7
Resolution
When you insert an Advantys island as a slave in the 'Sycon' software, only the first four (4) RxPDO's
and TxPDO's are enabled.
If you enable any of the other 'PDO's', the COB-ID's that Sycon assigns to 'TxPDO 5' through 'TxPDO yyy'
(i.e., TxPDO 12, etc.) or 'RxPDO 5' through 'RxPDO xx (i.e., RxPDO 12, etc.) could be outside of the range
specified by the DS301 version 4.02 'CANopen Application Layer and Communication Profile'
specification. If this happens, the CANOPEN run light on the NCO2212 will stay blinking even if
the correct CANOPEN network address is configured for the module.
The following table is from the 'CANopen Application Layer and Communication Profile' specification
DS301 version 4.02.
To resolve the problem:
- Open the Sycon configuration.
- Deselect the checkbox next to 'Automatic COB-ID allocation in accordance with profile 301'.
- Change the COB-ID to a number that is within range of the specification. (.e., 1180 to 1185)
- Click OK to save the changes and close the 'Node Configuration' window.
- Save the 'Sycon' configuration.
- Update the Unity application by clicking on 'refresh'
- Save the changes.
- Build the Unity application.
- Transfer the Unity application to the PLC.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.