Issue
Custome would like to transfer native device configuration from one EGX to another
Product Line
EGX300
Environment
EGX300, Internet Explorer, Firefox, Chrome
Cause
Customer doesn't want to recreate the configuration
Resolution
Yes, It is possible. Follow the instructions below
1. Both EGX's need to be on the same Firmware. Strongly suggested that you also have the same Disk Update version on each.
2. With an Administrator account, FTP into the (Primary) EGX300 and copy the file named egx300cfg.txt from the root. I suggest that you save this to your PC keeping the same name.
3. (Best Practice) - This step is not mandatory; however, I would propose that you make a backup copy of the (Secondary) EGX file namedegx300cfg.txt for your safe keeping. This will be overwritten once you make the copy.
4. With an Administrator account, FTP the file named egx300cfg.txt from your PC, to the (Secondary) EGX300 root directory.
5. This will cause your EGX300 to reboot.
What is replicated?
The register list in the EGX300...
The top banner text and color of the EGX300.
The Device List...already configured like the Primary.
The same User accounts
Note: A free FTP client like FileZilla can be use to transfer the files to the different EGX300. The same procedure can be follow if this is used
Đã phát hành cho: Schneider Electric Việt Nam








Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.