Example of the STRING_TO_x block in FBD using Control Expert (formerly Unity Pro ) .
Goals and Symptoms
This resolution is intended to outline the operation of the STRING_TO_x blocks from Control Expert (formerly Unity Pro) instruction set
Causes and Fixes
The STRING_TO_x blocks will convert strings of ASCII decimal characters stored in multiple contiguous registers into one tag.
The Unity Pro instruction set has three blocks
STRING_TO_INT
STRING_TO_DINT
STRING_TO_REAL
For this application, we will use the INT version.
Two tags are created:
String_In of type STRING located at %MW1 and
Int_Out type INT located at %MW100.
String_In occupies %MW1-%MW3
Each byte of the memory words contain one ASCII decimal character. These ASCII decimal characters are converted into one integer value containing the integer equivalents located at %MW100.
If the String_In is pulled up in the animation table you will see something like the example below:
If the three occupied %M's are pulled up in the animation table you will see the individual characters; two ASCII decimal characters per %MW:
The converted string is shown below both by pulling the tag and the %MW location itself:
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.