Goals and Symptoms
TSXETG3010
M340
Window XP Pro SP2
Causes and Fixes
In order to bridge through a TSXETG3010 you must first configure a modem network connection on your PC.
Open Network connections by going to Start>Settings>Network Connections
Next chose create new connection
This opens the New connection wizard. Press Next.
Choose "Connect to a network at my workplace" and press next.
Pick a dial-up connection and press next.
Give the connection a name and press next.
Type in the phone # of the TSXETG3010.
Press next.
Choose the connection availability and press next.
Press Finish to complete the connection setup.
To test the connection remove the Ethernet cable from you PC and attach your PC's internal modem to the phone line.
Go to Start>Settings>Network Connections> ETG3010 (or whatever you named your connection).
A connection window should open. Using the username and password USER and USER dial the connection.
Once a connection is established you should see it displayed in your system tray.
Verify the connection by logging into the embedded web pages of the TSXETG3010.
Open Internet explorer and type in the IP address of the TSXETG3010.
Since your Ethernet cable is unplugged your only connection is through the modem.
Open your Unity project and go to PLC>Set address.
Choose TCP/IP as the media and type in the IP address of the TSXETG3010 but after the IP address use a semi-colon (;) followed by the M340 modbus address.
Press OK.
To connect go to PLC>Connect
Đã phát hành cho: Schneider Electric Việt Nam






Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.