What is the maximum number of registers the Modbus Device Importer (MDI) can configure and support?
Issue
What is the maximum number of registers the Modbus Device Importer(MDI) can configure and support?
Product Line
ION Enterprise 5.6
ION Enterprise 6.0
SPM 7.0.1
PME 7.2.x
PME 8.x
Cause
User would like to know maximum number of registers the Modbus Device Importer(MDI) can be configured and supported.
Environment
Creating device type thorough Modbus Device Importer (MDI)
Resolution
When configuring MDI, user will have to create Managers then Modules and then registers. Therefore, they each have their own limitation as described below.
User can have maximum of 128 Managers, 4095 modules per each manager, and 255 registers per each module(by convention).
It is possible to have multiple managers of the same type in the MDI (the translators definitely don't care about this).
These limits are for compatibility with the MDI, to make it easier to validate what is an unused handle when automatically allocating new handles.
NOTE: In previous versions of the MDI the maximum was around 300-400 registers total. This limit was removed in version 5.6 of ION Enterprise when extensions logging support was added to the MDI.
Later versions of PME 9.0 and above now uses Device Type Editor
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.