How do you perform a soft reset on a CM3000/4000 and PM8 series?


Issue:
Unable to power cycle the meter physically. Need to do remotely or perform soft reset by writing modbus register to the meter.

Product Line:
CM3000/4000, PM8 series

Causes:
Sometimes local access to where the meters are installed isn't possible or access to the wiring of the meter is blocked.

Resolution:
In this case, remotely write modbus register to meter in order to power cycle the meter. Using software like Tester (software the read/write register):

Write 9020 to register 8000
Then, write 1110 to register 8000

This will reset the meter.

In addition, the PM8 series meter you can write modbus register from front panel. Also, if user has CM3000/4000 with display, they can also write modbus register from front display.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:

Bạn cần trợ giúp?

  • Công cụ chọn sản phẩm

    Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.

  • Nhận báo giá

    Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.

  • Nơi mua hàng?

    Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.

  • Trung tâm Hỗ trợ

    Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.

  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings