Issue:
Operating temperature range for the Altistart 22
Product Line:
ATS22, Altistart 22
Environment:
All models, all serial numbers.
Cause:
high or low ambient temperatures.
Resolution:
The standard current ratings for the ATS22 is based on an ambient temperature of 40C (104F).
The minimum operating temperature is -10C (14F). The maximum operating temperature is 60C (140F).
When operating above 40C (104F), the softstart needs to be derated by 2.2% for every degree Celsius above 40C (104F).
For example: ATS22D32S6U is 32A rated. For an ambient temperature of 50C (122F), derating is 22% (2.2 x 10). The 32A softstart rating becomes 24.96A (32A x 0.78 = 24.96).
Operating temperature range for the Altistart 22
Product Line:
ATS22, Altistart 22
Environment:
All models, all serial numbers.
Cause:
high or low ambient temperatures.
Resolution:
The standard current ratings for the ATS22 is based on an ambient temperature of 40C (104F).
The minimum operating temperature is -10C (14F). The maximum operating temperature is 60C (140F).
When operating above 40C (104F), the softstart needs to be derated by 2.2% for every degree Celsius above 40C (104F).
For example: ATS22D32S6U is 32A rated. For an ambient temperature of 50C (122F), derating is 22% (2.2 x 10). The 32A softstart rating becomes 24.96A (32A x 0.78 = 24.96).
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.