How do I disable the Line Contactor on the E-Flex

Issue:
Customer wants to keep the line contactor in the circuit to allow the drive to decelerate verses freewheel stop.

Product Line:
E-Flex

Environment:
E-Flex with modification B09 (line contactor).
Cause:
The line contactor opens when the run command is removed.
Resolution:
There is no documentation / data to support this reconfiguration of the original design. This could possible have an effect on the drive ratings. Caution: This procedure should only be performed while power has been removed from the E-Flex.
Place a jumper between terminals 4 and 11.  This circuit modification will keep the line contactor closed when the switch is in the AFC position.  The line contactor will remain open when the switch is in OFF or BYPASS.

Schneider Electric Việt Nam

Bạn cần trợ giúp?

  • Công cụ chọn sản phẩm

    Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.

  • Nhận báo giá

    Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.

  • Nơi mua hàng?

    Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.

  • Trung tâm Hỗ trợ

    Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.

  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings