Issue:
Is there a way to adjust the torque to get the motor moving from a start position?
Product line:
Altistart 22, ATS22
Environment:
All models, all serial numbers
Cause:
The default settings in the ATS22 cannot produce enough torque to ramp up the Soft Starter, which could lead to overcurrent, overload or excessive starting time faults.
Resolution:
Increasing the parameters below can aid in providing more breakaway torque to get the motor moving and up to speed.
SET Menu:
Parameter T90 - Initial Voltage. This value is adjustable from 10% to 50% of the full voltage, in increments of 5%. Factory setting is 30%.
Parameter ILt - Current limit. This is the maximum current allowed during the startup. It is adjustable up to 700% of the Motor Rated Current (In parameter). The maximum value is 350% of the Soft Starter rated current (IcL parameter). Factory setting is 350%.
ADJ Menu: (To access the ADJ menu, LAC parameter under the SET menu must be set to "on")
Parameter bSt - Boost Time. This provides an 80% pulse of the Line voltage (UIn parameter) for 0.0 to 1.0 seconds. Factory setting is 0.0.
Is there a way to adjust the torque to get the motor moving from a start position?
Product line:
Altistart 22, ATS22
Environment:
All models, all serial numbers
Cause:
The default settings in the ATS22 cannot produce enough torque to ramp up the Soft Starter, which could lead to overcurrent, overload or excessive starting time faults.
Resolution:
Increasing the parameters below can aid in providing more breakaway torque to get the motor moving and up to speed.
SET Menu:
Parameter T90 - Initial Voltage. This value is adjustable from 10% to 50% of the full voltage, in increments of 5%. Factory setting is 30%.
Parameter ILt - Current limit. This is the maximum current allowed during the startup. It is adjustable up to 700% of the Motor Rated Current (In parameter). The maximum value is 350% of the Soft Starter rated current (IcL parameter). Factory setting is 350%.
ADJ Menu: (To access the ADJ menu, LAC parameter under the SET menu must be set to "on")
Parameter bSt - Boost Time. This provides an 80% pulse of the Line voltage (UIn parameter) for 0.0 to 1.0 seconds. Factory setting is 0.0.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.