EM64XX THD issue
Goals and Symptoms
Summary
EM64XX THD issue in Meter display and through communication.
Symptoms
The EM64XX power meter shows current THD% as ----in the meter display and -999 through communications.
Causes and Fixes
Cause
1. When the secondary current is less than and equal to 10% or greater than and
equal to 110% of CT ratio.
2. When frequency is greater than 65Hz.
Resolution
In order to get the THD reading proper we need to maintain
1. Secondary current should be greater than 10 % and should be less than 110% of CT ratio.
2. Frequency should be less then 65 Hz.
All the necessary information is available in User Manual and QSG.
Goals and Symptoms
Summary
EM64XX THD issue in Meter display and through communication.
Symptoms
The EM64XX power meter shows current THD% as ----in the meter display and -999 through communications.
Causes and Fixes
Cause
1. When the secondary current is less than and equal to 10% or greater than and
equal to 110% of CT ratio.
2. When frequency is greater than 65Hz.
Resolution
In order to get the THD reading proper we need to maintain
1. Secondary current should be greater than 10 % and should be less than 110% of CT ratio.
2. Frequency should be less then 65 Hz.
All the necessary information is available in User Manual and QSG.
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.