Issue:
The run Time Indicator (RTH parameter) in the ATV61/71 series drives action in sleep / Low speed timeout mode
Product Line:
Altivar 61 and Altivar 71 series drives.
Environment:
Units with or without PID enabled in which the Low-Speed Timeout function (TLS) is utilized.
Cause:
Clarification of the function is needed.
Resolution:
The elapsed run time counter does continue to increment when the Low-Speed Time Out function has been activated. Even though the motor is not turning, the drive is considered to be in a run mode and the elapsed run time counter continues to run. In order to stop the run time indicator from counting, the run command will need to be removed from the drive.
The run Time Indicator (RTH parameter) in the ATV61/71 series drives action in sleep / Low speed timeout mode
Product Line:
Altivar 61 and Altivar 71 series drives.
Environment:
Units with or without PID enabled in which the Low-Speed Timeout function (TLS) is utilized.
Cause:
Clarification of the function is needed.
Resolution:
The elapsed run time counter does continue to increment when the Low-Speed Time Out function has been activated. Even though the motor is not turning, the drive is considered to be in a run mode and the elapsed run time counter continues to run. In order to stop the run time indicator from counting, the run command will need to be removed from the drive.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.