Issue:
Set up the drive to fallback to set speed when it drops its network connection
Product Line:
Altivar ATV61 ATV71 using serial communications
Environment:
All
Cause:
Wants to the ATV61 drive to fallback to a fixed speed when the drive drops its network connection.
Resolution:
You can program the drive to do a fallback speed under network fault manager in menu 1.8 FLT management.
Programming
Set your Access level to Advanced in the Main Menu.
Menu 1.8 FLT menu
Com fault manager enter
Network fault manager set to LFF or Fallback speed.
Set up the drive to fallback to set speed when it drops its network connection