Video: Why I am seeing only 2 components of phasor diagram of my delta connected ION meter in ION Setup's phasor view?
Issue
For a delta connected ION meter, the phasor diagram in ION Setup (ION Setup>Setup Assistant>Verification>Wiring>Phasor Viewer), shows only 2 components: (for voltage) V 12 and V 32, (for current) I1 and I3.

Where are the V23 and I2?

Combined Phasor Viewer
Side by Side Phasor Viewer



Product Line
PM8000, ION7650/7550/7500/7600/73xx/86xx/8500/8400/8300
ION Setup 3.0.x

Environment
ION Setup>Setup Assistant>Verification>Wiring>Phasor Viewer

Cause
ION Setup provides 2 ways to view the phasor diagram for a delta connected ION meter:
Instrument (60 Delta)
System (120 Delta)

Instrument view corresponds to how an electrician wants to see it (are the meter voltage and current inputs correctly wired up) whereas, system view corresponds to how the phasor diagram should look like on the primary side of the measured system.

By default, the instrument view is selected.
Options


Resolution
Please go to the ION Setup menu bar>Tools>Options>Conventions>Delta Vector Display>(change it to)System (120 Delta).



Options
Combined Phasor viewer
Side by Side Phasor Viewer

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings