Issue
Cannot display persistent variable in the embedded web page of some factory cast modules when opening Data editor, graphic viewer and graphic editor
Product Line
Factory cast HMI (WMY, NMW), Factory cast gateway (TSXETG30xx)
Resolution
Additional Information
Principle of HORB communication
Cannot display persistent variable in the embedded web page of some factory cast modules when opening Data editor, graphic viewer and graphic editor
Product Line
Factory cast HMI (WMY, NMW), Factory cast gateway (TSXETG30xx)
Resolution
- HORB communication is only used for FactoryCast HMI module (WMY, NWM) and FactoryCast Gateway (TSXETG30xx), not for others FactoryCast modules (NOE, ETY, ETG1000 ...)
- For FactoryCast HMI modules : all the variables are persistent; for FactoryCast modules: all the variables are non-persistent; for FactoryCast Gateway modules (TSXETG30xx): we can have both persistent and non persistent variables.
- When we want to display persistent variables in the embedded web page of the FactoryCast gateway (TSXETG30xx) module, only the data editor lite will display those variable because it uses the ModbusTCP/IP communication (port502). For persistent or non-persistent variables, the data editor, Graphic viewer and Graphic editor do not use the same communication protocol:
Additional Information
Principle of HORB communication
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.