A user would like to know the various reasons behind the status LED's on an Enercept Meter.
Product Line
Enercept Meters
Environment
Enercept meter troubleshooting
Cause
The Enercept meter has a status LED for diagnostic purposes. A user would like to know more information about the various states of the status LED for troubleshooting.
Resolution
If the LED blinks green | The product is functioning normally. It blinks slow, approximately one second on, then one second off. |
If the LED is red and blinking slowly | In most cases, incorrect wiring will cause the STATUS LED to blink RED (slowly). However, a power factor lower than 0.5 could cause the LED to blink this way, even if the unit is installed properly. |
If the LED is red and blinking quickly | CT’s maximum current rating has been exceeded |
If the LED does not blink | Check fuses and voltage connections. STATUS LED should blink regardless of CTs, Modbus connections, and DIP switch settings. |
If the LED does not blink. | When the unit is wired on the load side of an adjustable frequency drive and the LED does not blink, the unit’s thermal fuse could be blown. The unit must not be installed on the load side of an adjustable frequency drive. |
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Bắt đầu ở đây!
Tìm câu trả lời ngay. Tự tìm kiếm giải pháp, hoặc kết nối với một trong các chuyên gia của chúng tôi.
Liên hệ hỗ trợ
Liên hệ với nhóm chăm sóc khách hàng của Schneider để nhận thêm thông tin, được hỗ trợ kỹ thuật, trợ giúp khiếu nại và các thông tin khác.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Tìm kiếm câu hỏi thường gặp
Nhận câu trả lời bạn cần bằng cách duyệt tìm những Câu hỏi thường gặp (FAQ) liên quan đến chủ đề.
Liên hệ bộ phận bán hàng
Đăng ký bán hàng trực tuyến và chuyên gia của chúng tôi sẽ liên hệ với bạn.