Issue:
Accessing webpage on ATV61 ATV71 VFDs.
Product Line:
Altivar 61 and 71 drives
Environment:
All models and serial numbers with Ethernet IP option card VW3A3316
Cause:
Java 1.8 is not supported or web server services are not activated.
Resolution:
First, verify that web server services are activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Đã phát hành cho: Schneider Electric Việt Nam