Issue:
Damper control configuration on the ATV212 series drive
Product Line:
Altivar 212 series drives.
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
Cause:
Damper control configuration assistance needed with this drive.
Resolution:
Damper control on the ATV212 drive requires 3 settings to be adjusted. You need to configure a relay output to control the damper, then you need to configure a logic input to monitor the damper status via the damper end switch, and finally the parameter F580 needs to be configured for the type of feedback switch your damper has. See details from the ATV212 Programming manual below:
NOTE: Damper Control in the enclosed ATV212 S-Flex drive package is managed differently. Consult the S-Flex documentation for details.
Damper control configuration on the ATV212 series drive
Product Line:
Altivar 212 series drives.
Environment:
All models and serial numbers with firmware revision 1.5 or greater.
Cause:
Damper control configuration assistance needed with this drive.
Resolution:
Damper control on the ATV212 drive requires 3 settings to be adjusted. You need to configure a relay output to control the damper, then you need to configure a logic input to monitor the damper status via the damper end switch, and finally the parameter F580 needs to be configured for the type of feedback switch your damper has. See details from the ATV212 Programming manual below:
NOTE: Damper Control in the enclosed ATV212 S-Flex drive package is managed differently. Consult the S-Flex documentation for details.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.