Issue:
SCF1 fault on the ATV32 drives.
Product Line:
Altivar ATV32
Environment:
All
Cause:
ATV32 is tripping on SCF1 when they try and run the motor.
Resolution:
SCF1= Motor short circuit
Remedy to try=
Check cables going to the drive and the motor insulation.
Try reducing the switching frequency.
Try connecting a Line reactor in series with the input of the drive.
Check the adjustment of the speed loop and brake.
Try increasing the switching frequency
You can also ways disconnect the motor and turn off the OPL ( output phase loss protection) and run the drive open circuit without the motor at 20 hz 40 hz and 60 hz.
SCF1 fault on the ATV32 drives.
Product Line:
Altivar ATV32
Environment:
All
Cause:
ATV32 is tripping on SCF1 when they try and run the motor.
Resolution:
SCF1= Motor short circuit
Remedy to try=
Check cables going to the drive and the motor insulation.
Try reducing the switching frequency.
Try connecting a Line reactor in series with the input of the drive.
Check the adjustment of the speed loop and brake.
Try increasing the switching frequency
You can also ways disconnect the motor and turn off the OPL ( output phase loss protection) and run the drive open circuit without the motor at 20 hz 40 hz and 60 hz.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.