Issue:
E-19 on display
Product Line:
ATV212
S-Flex enclosed ATV212
Environment:
All models and serial numbers
Cause:
Communication error between control CPU's
Resolution:
This is a CPU Communications Error
In certain cases, high switching frequency (F300: Switch. freq. level) may contribute to an E-19 error, so if all the above had been confirmed and the issue remains, change F300 to 6 kHz and test.
If issue remains,
E-19 on display
Product Line:
ATV212
S-Flex enclosed ATV212
Environment:
All models and serial numbers
Cause:
Communication error between control CPU's
Resolution:
This is a CPU Communications Error
- Check the environment (electromagnetic Compatibility or EMC).
- Ensure proper grounding of the drive and the motor.
- Ensure proper separation of control and communication wiring from power wiring (line and load).
- Use shielded cable for analog and serial communication and follow proper shielding/grounding practices.
In certain cases, high switching frequency (F300: Switch. freq. level) may contribute to an E-19 error, so if all the above had been confirmed and the issue remains, change F300 to 6 kHz and test.
If issue remains,
- Power down and after the display is blank, remove all control wiring and then reapply power and see if the fault returns.
- Check that no external +24v supply is connected to the control terminals. If external 24V is used, disconnect it and then test to see if it may be a source of noise.
- With no power applied, check internal connections on the control terminals as well as the connection between circuit boards that are visible without disassembly.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.