Issue:
Why isn't the ATV212 drive in the S-Flex enclosure powering up when the selector switch is in the AFC position?
Product Line:
Altivar ATV212 S-flex enclosed with bypass option and B07 mod
Environment:
All
Cause:
Line contactor is not pulling in to power up the variable speed drive.
Resolution:
- Check to see if the red power LED is powered on the outside of the enclosure. If this red power LED is on, then we know the CPT and fuses are all good.
- Check to see if the Line contactor is pulled in. If the line contactor is not pulled in, check the control circuit to see what might be not allowing the contactor to pull in.
- Check to see if the bypass circuit works by putting the AFC/Off/Bypass switch in bypass mode.
- If the bypass contactor is not pulling in, and the line contactor is not pulling in, check to see if the OLR has tripped and needs to be reset.
- Check for loose connections in the 120VAC control wiring in the S-Flex enclosure.
Review the wiring diagrams in the S-Flex manual for details on how the drive cabinet is wired.
https://www.se.com/us/en/download/document/30072-451-83/
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team. If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.