Why does Vijeo Designer report Error 2897 when I build the application?

Issue:
Somachine / Vijeo Designer reports Error 2897 when I build the application when I only have one device connected to COM1.

Product Line:
Vijeo Designer (all versions), SoMachine (all versions)

Resolution:
This build error occurs in Vijeo Designer when SoMachine has the "SoMachine_Network_Manager" added under COM1 of Somachine configuration.
Why does Vijeo Designer report Error 2897 when I build the application?
To resolve this issue, delete the SoMachine_Network_Manager under COM1 in Somachine and the Vijeo Designer application will build properly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings