Clicking on the Settings link on the Power Monitoring Expert main page pops up an error window
Issue
When I use clicks on the "Settings" link on the Power Monitoring Expert main page a new error window pops up with link to GeneralSettingsDialog.html not found

Product
Power Monitoring Expert (PME) 8.1

Environment
Main web site is using non default address like /PQweb instead of the default /web

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).*

1) Navigate to [PME install]\Applications\ApplicationFramework\content
2) Backup the file GeneralSettingsDialog.js
3) Edit the original file with a text editor
Replace the line TemplateUtil.LocAndLoad('/Web/Content/GeneralSettingsDialog.html', with the correct with the setup URL
For example
TemplateUtil.LocAndLoad('/PQWeb/Content/GeneralSettingsDialog.html',
4) Close all web clients an restart IIS
5) Verify that the link now open the settings page.

Schneider Electric Việt Nam

Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
  • Tài liệu về Sản phẩm
  • Tải xuống phần mềm
  • Công cụ chọn Sản phẩm
  • Thay thế và thay đổi sản phẩm
  • Trung tâm Hỗ trợ
  • Tìm Văn phòng của chúng tôi
  • Nhận báo giá
  • Tìm Nhà Phân phối
  • Cộng đồng Schneider Electric
  • Cơ hội nghề nghiệp
  • Hồ sơ doanh nghiệp
  • Báo cáo hành vi sai trái
  • Khả năng truy cập
  • Phòng tin tức
  • Nhà đầu tư
  • EcoStruxure
  • Tìm việc
  • Blog
  • Chính sách bảo mật
  • Thông báo về Cookie
  • Điều khoản sử dụng
  • Change your cookie settings