Issue:
ATV212 not following customized ramp-up and ramp-down parameters.
Product Line:
Altivar 212
Environment:
All
Cause:
Not following ramping setup
Resolution:
Press mode to go to AUF.
Arrow down to ACC and enter. This is the ramp up time the drive will follow upon run command.
Go into AU1 and enter. Set it to 0 to deactivate auto ramp and follow your ramp up time.
Set AU1 to 1 to allow the drive to follows its own auto ramp up time.