ENM Monitoring and Diagnostics pages display "[Invalid Date]" for timestamps
Issue
The Event Notification Module (ENM) Monitoring and Diagnostics pages display [Invalid Date] in timestamp columns instead of the actual timestamp.
Product Line
ENM 8.3.x
Environment
PowerSCADA Expert 8.1
Power Monitoring Expert 8.1
Cause
Some Windows locales use special characters for AM/PM notation (e.g., Italian [Switzerland], Chinese [Singapore]). When Windows is configured to use one of these locales, ENM cannot properly format timestamps, resulting in [Invalid Date].
Resolution
Change the Windows locale to one that uses standard AM/PM characters.
Examples:
- Italian (Italy)
- Chinese (China)
Steps:
- Open Control Panel → Region and Language.
- Change the locale to a supported setting.
- Restart ENM services if necessary.
Notes
- This issue applies only to ENM 8.x and PME 8.1.
- Newer versions of PME and ENM have resolved this locale parsing issue.
Recommendation
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Đã phát hành cho: Schneider Electric Việt Nam
Tìm hiểu thêm
Phạm vi:
Tìm hiểu thêm
Phạm vi:
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.