Some of the Sepam 80 protection functions can be used for low-voltage installations, as explained in the Protection Functions User Manual.
However, some of the limitations in terms of supported wiring configurations are not explicitly stated in the user manual.
Also - there are not always warning in SFT2841 to inform the user that a certain configuration is not possible.
Please see the attached file for an example where the 64REF, 51N, and 51G protection functions cannot be achieved using a single Sepam 80 relay. In fact, the protection functions could be applied correctly with a single relay, but some wiring modifications are required.
As explained in the attached file, the key points to keep in mind are as follows:
- for a 4-wire low-voltage system (e.g., TN-C, or TN-S), the CT's used for 51N and 51G should not be the same. They should be installed at different positions.
- all supported configurations for the 64REF function in low-voltage use the CCA634 CT adaptor. So, the corresponding Io input (for the CSH120/200) cannot be used.
- the SFT2841 software (as of version 15.1) does not give any warnings if you create a configuration which enables all of these functions. It is assumed that the project team will check the wiring to ensure that the CSH120/200 (Io) input will not be used if a CCA634 is installed, for example.
AEDL3
However, some of the limitations in terms of supported wiring configurations are not explicitly stated in the user manual.
Also - there are not always warning in SFT2841 to inform the user that a certain configuration is not possible.
Please see the attached file for an example where the 64REF, 51N, and 51G protection functions cannot be achieved using a single Sepam 80 relay. In fact, the protection functions could be applied correctly with a single relay, but some wiring modifications are required.
As explained in the attached file, the key points to keep in mind are as follows:
- for a 4-wire low-voltage system (e.g., TN-C, or TN-S), the CT's used for 51N and 51G should not be the same. They should be installed at different positions.
- all supported configurations for the 64REF function in low-voltage use the CCA634 CT adaptor. So, the corresponding Io input (for the CSH120/200) cannot be used.
- the SFT2841 software (as of version 15.1) does not give any warnings if you create a configuration which enables all of these functions. It is assumed that the project team will check the wiring to ensure that the CSH120/200 (Io) input will not be used if a CCA634 is installed, for example.
AEDL3
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.