Steps to Activate Digital Output 2:
Based on the Command List, command to be send is 6003 to energize the output and command 6002 to de-energize.
Before sending the command be sure:
Unprotected Command Interface:
Based on the Command List, command to be send is 6003 to energize the output and command 6002 to de-energize.
Before sending the command be sure:
- The Digital Output is not assigned to an Alarm
- The Digital Output is configured to be controlled remotely/external
- Connect to the PM Meter with IP address of the Gateway and the unit ID
- READ ONLY ONCE REGISTER 405680 (5679)
- Value should be Unsigned integer different from 0
- Note this value (for example 12345)
- WRITE A BLOCK OF 3 REGISTERS STARTING ADDRESS 405000 (4999)
- Register 405000 (4999) should have Value 6003
- Register 405001 (5000) should have Value of the Semaphore (our example 12345)
- Register 405002 (5001) should have the ID of the Digital Output (2 for DO2)
- READ ONLY ONCE REGISTERS 405126 (5125) to confirm the result (should be 0 for Valid Operation)
Unprotected Command Interface:
- Connect to the PM Meter with IP address of the Gateway and the unit ID
- WRITE A BLOCK OF 3 REGISTERS STARTING ADDRESS 405250 (5249)
- Register 405250 (5249) should have Value 6003
- Register 405251 (5250) should have Value of 0
- Register 405252 (5251) should have the ID of the Digital Output (2 for DO2)
- READ ONLY ONCE REGISTERS 405376 (5375) to confirm the result (should be 0 for Valid Operation)
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.