Issue:
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
Đã phát hành cho: Schneider Electric Việt Nam


Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.