Issue:
Permanent magnet setup for synchronous motor on Process Drives.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Altivar 6xx Series:
This Function is available from V1.2. In ATV6XX drives earlier, it was not included, and the settings remains same as below.
Altivar 9xx Series:
To program the drive with a Permanent Magnetic Synchronous Motor
Permanent magnet setup for synchronous motor on Process Drives.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Altivar 6xx Series:
This Function is available from V1.2. In ATV6XX drives earlier, it was not included, and the settings remains same as below.
Altivar 9xx Series:
To program the drive with a Permanent Magnetic Synchronous Motor
- Set Motor Control Type - [Complete settings] [Motor parameters] [Motor Control Type] Ctt
- [Sync. mot.] Syn - Open-loop synchronous motors: Motor control type specific for permanent magnet synchronous motors.
- [Sync.CL] FSy - Open-loop synchronous motor: For motors with Encoders or motors with sinusoidal electromotive force (EMF) only
- [SYN_U VC] SYnU - Open-loop synchronous motor: This motor control type is used for variable torque applications.
- [Rel. Mot.] - Synchronous Reluctant Motor: Opened loop synchronous motor without permanent magnet. This motor control type is used for variable torque applications.
- Setup Motor data parameters - [Complete settings] [Motor parameters] [Motor data]
- [Sync Nominal I] nCrS - Sync motor nominal current.
- [Nom SyncMotor Speed] nSPS - Nominal synchronous motor speed.
- [Nom Motor torque] tqS
- [Pole pairs] PPnS
- [Angle setting type] ASt - Automatic angle setting type.
- [SyncMotor Stator R] rSAS
- [Sync Nominal Freq] FrSS - Synchronous motor nominal frequency.
- For Motors with Encoder you may need to perform an Angle Test
- See [Complete settings] [Motor parameters] [Motor data] [Angle test setting]
- Perform Autotune - [Complete settings] [Motor parameters] [Motor data] [Motor tune]
- When performing autotune make sure motor is connected
- Make sure motor is cooled down.
Đã phát hành cho: Schneider Electric Việt Nam




Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.